STANDARD

High quality insulation materials for special applications.

Test results according to SABS 0177: 
Non combustible SABS 0177 part v 
Surface fire index SABS 0177 part iii 
Spread of flame index 0 
Heat contribution index 0 
Smoke emission index <0.1% 
Surface fire index 0 
Class 1


Fire protection of steel columns in buildings. SABS 0177 – 11

Fireshield 5:
After 120 minute test highest temperature reached in steel column was 314°C.

Fireshield 3:
After 120 minute test highest temperature reached in steel column was 384°C.

Petroshield:
Protection of steel columns in hydrocarbon furnaces. SABS 0177 – 11

Cableshield:
Protection of cable trays in hydrocarbon fires. SABS 0177 – 11

Panelshield:
Fire protection panels. Suitable for use as a transformer fire shield. Tested by CSIR - building technology division.

Fibreshield:
Insulating plaster applied over fibre insulated ducting for weather protection. Can be painted.

 

 

INSULATION

 

Isoplast 350:
Cast thermal insulation.
Document protection.

Isoplast 500:
Cast or plaster.
For indoor use only.

Isoplast 700:
Cast spray or plaster application.
Suitable for internal or external use.

Isoplast 1050:
Cast spray or plaster application.
Suitable for internal or external use.
High strength high shear base for tile or veneer.

Application:
Sound insulation plaster for indoor use.